Level Transmitters>> STK633S |
|
|
Name: |
|
Level Transmitter with silicon sensor STK633S |
|
Type: |
|
STK633S |
|
Specifications: |
|
· Measuring:0 ~10mmH2O ~20mH2O
· Sensor:
Silicon sensor
· Output:4 ~20mA,1~5V
· Supply voltage:12~45V
· Accuracy:0.2%,0.25%,0.5%, |
|
|
|
|
|
|
|
Power supply (polarity protected) : |
|
* Supply voltage :12...45 VDC |
|
|
|
Output signal : |
|
* 2-wire-system : 4...20 mA with superimposed
signal for HART protocol digital communication
* 3-wire-system (optional): 1...5V
* Signal range: 3.8mA...22.8mA
* Signal on alarm : 3.8mA/ 22.8mA/Others on request |
|
|
|
Electrical protection : |
|
* Insulation resistance : >250M
* Short-Circuit protection : Permanent
* Reverse polarity protection : No damage, and no function
* Overvoltage protection : 500 V |
|
|
|
Performance : |
|
|
|
|
* Accuracy : |
|
Nominal range 0.2% |
|
0.25% accuracy for range trundown 1.5:1 |
|
0.5% accuracy for range trundown 2:1 |
* Power supply effect :Negligible
* Vibration effect :<0.01% of URL /g when tested 200Hz in any axis relative
* Thermal effect : ±0.15%/10K(-20~+70℃);
* Compensated temperature range of sensor: -30...80℃
* Permissible load: ≤50(V-12)Ω
* Stability: 0.1% FSO/Year
* Switch on delay : 5s
* Damping : 0 to 100s, step: 0.1s
* Response time: 200 ms (without consideration of electronic damping)
* Self stability configuration :0 to 2%
* Filter configured: 0 to 160 uA
* Communication resistance for HART protocol: Typ. 250 Ω |
|
|
|
Application conditions: |
|
* Humidity : 5...98%
* Ambient and operation : -30-85℃ (without display), -20-70℃ (with display)
* Storage : -30-85 ℃
* Ingress protection :IP 68
* Electromagnetic compatibility(EMC):Interference immunity and interference emission according
to GB/T17626.2-1998), compliance with IEC 61000-4-3:1995. |
|
|
|
|
|
|
|
|
|
|